Blowdown tanks are available for all steam boiler plant applications up to 100,000 PPH. All Tanks are manufactured to ASME code section VIII Div. 1.
751 to 100,000 PPH high pressure steam.
Design pressure 100 Psig (1035 Kpag).
Built per CSA code B-51.1, Par: 6.5 and ASME code section VIII Div. 1.
Design and Fabrication Codes
AMSE Section V111, Div. 1, Latest addenda.
CSA B 51 M 1995
For easy sizing, please provide the following information
Boiler steam evaporative capacity (kg/hr. or lbs/hr.)
Maximum boiler pressure.
Manufacturing and Material
Pressure vessel quality carbon steel.
Pressure tested mig welded seams.
Interior and Exterior Finishes
Outside: Brush cleaned and one coat of enamel primer.
Inside: Brush cleaned.
Vessels are fabricated C/W the following items
Steel structural legs.
Lifting lugs (where required).
Pressure vessel identification plate.
Manufacturers data reports.
Vessels are registered for installation across Canada.
Vessels are also available "U" stamped.
Standard Sizes For Blowdown Tanks
THERMOGENICS
PART NUMBER
CAPACITY
(lbs./hr.)
DIAMETER
(inches)
HEIGHT
(inches)
VOLUME
(cu.ft.)
BD-24
751 to 1,500
24
36
8.0
BD-30
1,501 to 3,000
30
42
15.0
BD-36
3,001 to 7,000
36
42
20.0
BD-36-H
7,001 to 13,000
36
48
25.0
BD-42
13,001 to 25,000
42
64
40.0
BD-48
25,001 to 100,000
48
64
60.0