Thermocoil 2000
Automatic Packaged Recirculating Coil Tube Generators for unattended operation in specific jurisdictions. Low and High Pressure Steam applications from 75 to 600 BHP

Capacity
75 BHP (736 kw) to 600 BHP
(5,885 kw) output.
Pressure
Standard 15 PSIG (1 BAR) to 500 PSIG
(34.5 BAR) or higher as specified.
Fuels
Natural Gas and Number 2 Oil.
Efficiency
Up to 85% efficiency with economizers.
Codes
ASME, NATIONAL BOARD or as specified. Complies with local code requirements as applicable.
Environmental Compliance with current noise and emissions regulations.
Design and Opperation Improvements
Redesigned combustion air blower for whisper
quiet operation.
PLC based multiple boiler lead lag control system
with optional DTAM operator, interface c/w percent modulation feedback allowing for each boiler to be operated at its maximum efficiency range at all times.
Multi blade damper on inlet to combustion blower provides lower excess air levels and radiation convection losses.
A new 4-20 ma Modulating Burner Control provides
more precise control and percentage feedback for
the PLC based Lead Lag control system.
New natural gas control systems provide greater
ease of combustion setup, higher combustion efficiencies and lower NOX levels.
Redesigned flue gas economizer available with
s/s wrapper sheets.
PLC based flame safeguard control system with optional expanded annunciator.
Optional pneumatic feedwater control systems.
Standard Equipment Features
Fully modulating burner with 8-1 turndown on
Natural Gas and Number 2 Oil.
All electrical boxes are oil/dust tight.
All electrical conduit liquid tight.
Switch controls and warning devises located in
a central control panel at the front of the boiler
skid for ease of operation and trouble shooting.
Separate high voltage side panel.
Combustion air blower at floor level for ease of inspection and maintenance.
All coils have individual monitoring sensors.
Recirculating pump and combustion blower direct drive.
Automatic timer controlled bottom blowdown.
Most service connections located at common junction point.
Manual continuous blowdown or optional
automatic TDS control available.
Double walled boiler shell preheats combustion air and cools outer casing, thereby minimizing radiation losses.
Steam separation drum guarantees 99% plus
dry saturated steam.
Heavy duty gauge glass assembly
Rear door access at floor level without disturbing refractory seal.
Fuel to steam efficiencies up to 85% with heat recovery.

Performance Data, Sizes and Dimensions*

RATED
BOILER
CAPACITY
B.H.P.
EQUIVALENT
EVAPORATION
PPH FROM &
AT 212°F
THERMAL
OUTPUT BTU/HR
(XCAL/HR)
X 1000
FLUE
OUTLET
CONNECTION
INCHES (mm)
APPROXIMATE
FUEL CONSUMPTION
DIMENSIONS
INCHES (mm)
APPROXIMATE
SHIPPING
WEIGHT
LBS (Kg)
NATURAL GAS
SCFH
#2 FUEL OIL
GPH (Lits/H)
L (A)
W (B)
H (C)
75 A
2,587
2,511
(633)
12
(305)
3,138
20
(91)
110
(2,794)
82
(2,083)
96
(2,438)
6,000
(2,721)
100 A
3,450
3,348
(844)
14
(356)
4,185
25
(114)
106
(2,692)
82
(2,083)
96
(2,438)
6,600
(2,994)
150 A
5,175
5,021
(1,265)
16
(406)
6,276
38
(173)
114
(2,896)
82
(2,083)
100
(2,540)
8,400
(3,810)
200 A
6,900
6,695
(1,687)
18
(457)
8,367
50
(227)
114
(2,896)
82
(2,083)
100
(2,540)
8,200
(3,727)
200 B
6,900
6,695
(1,687)
18
(457)
8,367
50
(227)
123
(3,124)
92
(2,337)
116
(2,946)
11,000
(4,990)
250 B
8,625
8,369
(2,109)
20
(508)
9,990
63
(286)
123
(3,124)
92
(2,337)
116
(2,946)
13,300
(6,033)
300 B
10,350
10,043
(2,531)
24
(610)
12,553
63
(286)
123
(3,124)
92
(2,337)
116
(2,946)
13,300
(6,033)
350 B
12,075
11,717
(2,953)
24
(610)
14,646
75
(341)
131
(3,327)
92
(2,337)
116
(2,946)
14,200
(6,441)
400 B
13,800
13,391
(3,374)
24
(610)
16,739
100
(455)
139
(3,530)
92
(2,337)
116
(2,946)
16,900
(7,666)
450 B
15,525
15,065
(3,795)
24
(610)
18,881
112
(511)
139
(3,530)
92
(2,337)
116
(2,946)
17,300
(7,846)
400 C
13,800
13,391
(3,374)
24
(610)
16,739
100
(455)
158
(4,013)
116
(2,946)
124
(3,150)
28,000
(12,954)
500 C
17,250
16,738
(4,218)
26
(660)
20,922
125
(568)
168
(4,267)
116
(2,946)
124
(3,150)
32,000
(14,515)
600 C
20,700
20,086
(5,062)
28
(711)
25,107
150
(682)
178
(4,521)
116
(2,946)
124
(3,150)
35,800
(16,239)
* Subject to change without notice. Oil fired available for #2 and diesel oil only.
*The descriptions and specifications contained in this website are approximate and were in effect at the time.
Thermogenics policy is one of continuous improvement and update. Changes to specific models may occur at anytime without notice or incurring any obligation.
Download the PDF version of this page.
RETURN TO THE TOP
Copyright © 2006 Thermogenics Inc. All rights reserved.