HOME PRODUCTS SERVICES CONTACT US
THERMOGENICS INC.
Thermocoil 2000
Efficient, Safe and Economical Process Heat,
up to 20,000,000 BTU/Hour Output


Forced Circulation, Multi-Coiled Tube, Forced Draft Fired.
Efficiency
Up to 84%
Multi-orificed by Thermogenics.
Air Atomized by Thermogenics.
Air Atomized Oil, Multi-orificed Gas by Thermogenics
Electric Spark Ignited, Interrupted Gas Pilot.
Up to 10:1 turndown.
Registered to ASME & CSA requirements, and Hydro approved.
Programmed Flame Safeguard Control with Ultra Violet Flame Detection. Individual Coil Temperature Control and Outlet Temperature Limits.
750°F design temperature, 250 PSIG.
Design and Opperation Improvements
No refractory combustion chamber, new membrane wall furnace.
4-20 ma Modulation for feed back to PLC based Lead/Lag Control.
Redesigned combustion air blower ensures quiet operation.
Complete flexibility on burner management systems.
Redesigned damper blades on combustion blower provide lower excess air levels.
Solid state coil temperature system with individual temperature readouts and set points.
Redesigned burner increases efficiency.
Optional linkagless control provides lower turndown rates and more sonsistent efficiencies across the modulating range.
Standard Equipment Features
Fully modulating burner with 10:1 turndown on
Natural Gas and #2 Oil.
All electrical boxes are oil/dust tight.
All electrical conduit liquid tight.
Switch controls and warning devises located in
a central control panel at the front of the boiler
skid for ease of operation and trouble shooting.
Separate high voltage side panel.
Combustion air blower at floor level for ease
of inspection and maintenance.
All coils have individual monitoring sensors.
Recirculating pump and combustion blower direct drive.
Quick response to load changes.
Most service connections located at common junction point.
Rapid start up from cold start.
Double walled boiler shell preheats combustion air and cools outer casing, thereby minimizing radiation losses.
Long life with minimal maintenance coils designed for 1000 PSIG.
Optional air or water cooled pumps
Rear door access at floor level without disturbing refractory seal.
Optional deaerator/expansion tanks.

Performance Data, Sizes and Dimensions*

RATED
BOILER
CAPACITY
B.H.P.
THERMAL
OUTPUT BTU/HR
(KCAL/HR)
X 1000
FLUE
OUTLET
CONNECTION
INCHES (mm)
APPROXIMATE
FUEL CONSUMPTION
DIMENSIONS IN
INCHES (mm)
FLUID
HEATER
CAPACITY
GALS (Lits)
APPROXIMATE
SHIPPING
WEIGHT
LBS (Kg)
NATURAL GAS
SCFH
#2 FUEL OIL
GPH (Lits/Hr)
L
W
H
75
2,511
(633)
12
(305)
3,138
20
(91)
114
(2,896)
94
(2,388)
87
(2,210)
50
(227)
5,700
(2,591)
100
3,348
(844)
14
(356)
4,185
25
(114)
114
(2,896)
94
(2,388)
87
(2,210)
58
(263)
6,300
(2,863)
150
5,021
(1,265)
16
(406)
6,276
38
(173)
120
(3,048)
94
(2,388)
91
(2,311)
75
(341)
8,100
(3,682)
200
6,696
(1,687)
18
(457)
8,367
50
(227)
131
(3,327)
100
(2,540)
101
(2,566)
110
(500)
10,700
(4,864)
250
8,369
(2,109)
20
(508)
9,990
63
(286)
131
(3,327)
100
(2,540)
101
(2,566)
135
(613)
13,000
(5,909)
300
10,043
(2,531)
24
(610)
12,553
63
(286)
138
(3,505)
100
(2,540)
101
(2,566)
160
(727)
13,900
(6,318)
350
11,717
(2,953)
24
(610)
14,646
75
(341)
160
(4,064)
102
(2,590)
101
(2,566)
185
(840)
16,600
(7,545)
400
13,391
(3,374)
24
(610)
16,739
100
(455)
164
(4,166)
124
(3,150)
116
(2,947)
290
(1,317)
28,100
(12,773)
500
16,738
(4,218)
26
(660)
18,881
112
(511)
176
(4,470)
126
(3,200)
116
(2,947)
350
(1,590)
31,600
(14,364)
600
20,086
(5,062)
28
(711)
16,739
100
(455)
188
(4,775)
126
(3,200)
116
(2,947)
410
(1,863)
35,400
(16,091)
* Subject to change without notice. Oil fired available for #2 and diesel oil only.
*The descriptions and specifications contained in this website are approximate and were in effect at the time of.
Thermogenics policy is one of continuous improvement and update. Changes to specific models may occur at anytime without notice or incurring any obligation.