Automatic Packages Once-Through Coil Tube Generators for unattended operation in specific jurisdictions. Low and High Pressure Steam applications from 40 to 200 BHP.
 |
40 BHP to 200 BHP output. |
 |
Standard 15 PSIG to 2700 PSIG |
|
|
Natural Gas and Number 2 Oil.
|
|
|
Up to 85% efficiency with economizers.
|
|
|
ASME, NATIONAL BOARD or as specified. Complies with local code requirements as applicable.
|
 |
Compliance with current noise and emissions regulations.
|
|
|
|
|
|
|
|
|
|
•
|
4-20 ma fuel/water system. no servo required.
|
•
|
4-20 ma modulation for feedback to PLC based Lead/Lag Control.
|
|
•
|
Redesigned combustion air blower ensures quiet operation.
|
•
|
Complete flexibility on burner management systems.
|
|
|
•
|
Solid state coil temperature system with individual temperature readouts and set points.
|
|
•
|
Redesigned burner increases efficiency.
|
|
|
•
|
PLC based flame safeguard with optional linkageless control.
|
•
|
Pneumatic by-pass control systems.
|
|
 |
|
|
|
|
|
•
|
Quick steaming 0-150 psi in less than 5 minutes.
|
•
|
High pressure quick disconnect hoses for ease
of maintenance. |
|
•
|
Fully modulating burner with 8-1 turndown on
Natural Gas and #2 Oil.
|
•
|
All electrical boxes are oil/dust tight. |
|
•
|
All electrical conduit liquid tight. |
|
•
|
Switch controls and warning devices located in a
central control panel at the front of the boiler skid
for ease of operation and trouble shooting.
|
•
|
Separate high voltage side panel. |
|
|
•
|
Heavy duty reciprocating triplex pump with
dampening device. |
|
•
|
Coils have monitoring sensors.
|
•
|
Most service connections located at common
junction point. |
|
•
|
Automatic timer controlled bottom blowdown.
|
|
|
•
|
Large face gauges.
|
•
|
Quiet compact design less than one quarter size
of conventional boilers. |
|
•
|
Steam separator guarantees 99% plus dry
saturated steam.
|
|
|
•
|
Fuel to steam efficiencies up to 85% with heat
recovery. |
|
•
|
Dry contacts for remote alarms.
|
|
|
|
•
|
Fuel to steam efficiencies up to 85% with heat recovery. |
|
  |
 |
|
 |
|
Performance Data, Sizes and Dimensions*
|
|
RATED
BOILER
CAPACITY
B.H.P.
|
EQUIVALENT
EVAPORATION
PPH &
AT 212ºF
|
THERMAL
OUTPUT BTU/HR (KCAL/HR)
X 1000
|
FLUE
OUTLET
CONNECTION
INCHES (mm)
|
APPROXIMATE
FUEL CONSUMPTION
|
DIMENSIONS IN
INCHES (mm)
|
APPROXIMATE
SHIPPING
WEIGHT
LBS (Kg)
|
|
NATURAL GAS
SCFH
|
#2 FUEL OIL
GPH (Lits/H)
|
L
|
W
|
H
|
|
40
|
1,380
|
1,339 (337)
|
10 (254)
|
1,675
|
12.0 (54)
|
84 (2,133)
|
48 (1,219)
|
80 (2,032)
|
4,000 (1,818)
|
|
65
|
2,240
|
2,176 (548)
|
10 (254)
|
2,680
|
19.0 (86.5)
|
84 (2,133)
|
48 (1,219)
|
80 (2,032)
|
4,000 (1,818)
|
|
100
|
3,450
|
3,348 (844)
|
13 (330)
|
4,185
|
30.0
(136.5)
|
87 (2,210)
|
60 (1,524)
|
82 (2,082)
|
5,300 (2,409)
|
|
150
|
5,175
|
5,021 (1,266)
|
15 (381)
|
6,276
|
45.0 (205)
|
96 (2,438)
|
60 (1,524)
|
109 (2,769)
|
7,200 (3,292)
|
|
200
|
6,900
|
6,695 (1,688)
|
18 (457)
|
8,367
|
50.0 (227)
|
96 (2,438)
|
63 (1,600)
|
106 (2,692)
|
7,700 (3,500)
|
|
|
* Subject to change without notice. Oil fired available for #2 and diesel oil only.
|
|
 |
 |
|
 |
|
*The descriptions and specifications contained in this website are approximate and were in effect at the time.
Thermogenics policy is one of continuous improvement and update. Changes to specific models may occur at anytime without notice or incurring any obligation.
|
 |
 |
|
|
Download the PDF version of this page.
|
|
|
 |
 |
|
|
|
|