HOME PRODUCTS SERVICES CONTACT US
THERMOHENICS INC.
Therm-O-Pac Packaged Deaertors
Therm-O-Pac Packaged Deaerators
produce water with an oxygen content
of less than .005cc per litre.
Engineered with versatility in mind.


Capacity 5,000 to 40,000 PPH. (Consult factory for larger units.)
Pressure Standard pressure design 100 PSIG (7 BAR); Standard operating pressure 2-30 PSIG (0.1-2 BAR)
Efficiency Produces water with an oxygen content of less than .005cc per litre.
Electrical Accessories Control panel to meet specifications. High Low Water Alarms and Lockouts (optional). Boiler feedwater pumps built to specifications.
Control Accessories Thermometers, Gauge Glass Assemblies, Overflow Drainers Pressure Reducing Valves, Make-up Control systems.
Packages Fully packaged systems on stand or non-packaged systems.
Therm-O-Pac System Diagram

Performance Data, Sizes and Dimensions*

MODEL
STORAGE CUBIC FEET
"A"
"B"
WEIGHT EMPTY
WEIGHT FLOODED
"A" SIZE
70
162 in.
48 in.
2,600 lbs.
12,800 lbs.
"B" SIZE
120
142 in.
60 in.
3,000 lbs.
17,000 lbs.
"C" SIZE
165
190 in.
60 in.
3,800 lbs.
22,500 lbs.
"D" SIZE
40
99 in.
48 in.
2,000 lbs.
8,300 lbs.
"E" SIZE
30
72 in.
48 in.
1,600 lbs.
6,200 lbs.
* Subject to change without notice.
Therm-O-Pac Deaerators Advantage
Engineered For Versatility

All units are available as pre-engineered total packages or as non-packaged. Besides reducing chemical cost, the Therm-O-Pac Deaerator limits steam losses to levels of less than .1 of 1%.

Thermo-O-Pac deaerators are ideally suited for use in small to medium sized steam plants. Thermogenics will also build custom sized units to fit specific space requirements and special storage capacities. Therm-O-Pac Deaerators are therefore ideally suited for retrofit in existing facilities or new installations. Deaerator packages ranging from 40,000 to 250,000 PPH are also available.
*The descriptions and specifications contained in this website are approximate and were in effect at the time.
Thermogenics policy is one of continuous improvement and update. Changes to specific models may occur at anytime without notice or incurring any obligation.
Download the PDF version of this page.